Navien · Boiler troubleshooting
Change gateway IP on wired Ethernet port
What is going on
Set the gateway IP over the Ethernet port through the FS-GUI network settings.
Check in this order
- Open the FS-GUI Network Settings landing page; the IP Settings tab is the default.
- Enable DHCP Client State to get an automatic IP, or enter IP Address, Netmask, Default Gateway and Domain Name Server 1/2 by hand.
- If the gateway is on a router, set the Default Gateway to the router's IP address.
- Click Update IP Settings, then click System Restart.
- Connect the gateway to the local network or router.
- If FS-GUI is open in a browser, point the browser at the new IP address before reconnecting.
Applies to: Gateway wired network settings
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Modbus/BACnet Gateway Start-up Guide, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.