Viessmann · Boiler troubleshooting

Connect boiler return mixing or isolation/modulating valve actuator (VD2/VD2A/CT3)

Vitotronic 100GC1

What is going on

Use a 120 V or 24 V valve adaptor. Valve run time is set by coding 40 between 5 and 199 seconds.

Check in this order

  1. Disconnect power to the control.
  2. Mount the 120 V or 24 V valve adaptor on the DIN rail inside the connection enclosure.
  3. Plug the gS plug into socket gS on the control.
  4. Secure the cable with a tie.
  5. Connect the black adaptor wire to terminal 8, 9 or 10 on the aBH DIN rail connection.
  6. Wire the valve actuator to the adaptor terminals as shown in the figures.

Applies to: VD2/VD2A/CT3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100, GC1 installation manual, p. 56. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.