Viessmann · Boiler troubleshooting
Connect boiler return mixing or isolation/modulating valve actuator (VD2/VD2A/CT3)
What is going on
Use a 120 V or 24 V valve adaptor. Valve run time is set by coding 40 between 5 and 199 seconds.
Check in this order
- Disconnect power to the control.
- Mount the 120 V or 24 V valve adaptor on the DIN rail inside the connection enclosure.
- Plug the gS plug into socket gS on the control.
- Secure the cable with a tie.
- Connect the black adaptor wire to terminal 8, 9 or 10 on the aBH DIN rail connection.
- Wire the valve actuator to the adaptor terminals as shown in the figures.
Applies to: VD2/VD2A/CT3
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100, GC1 installation manual, p. 56. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.