Direct exhaust sidewall vent termination: location and clearances
What is going on
Where the sidewall direct exhaust vent may exit the building. The SF-550 and SF-750 are condensing appliances, so flue products and condensate must be kept clear of people, openings and building surfaces.
Likely causes
- Termination too close to an air inlet, door, window or building surface
- Termination in a wind eddy or recessed area where flue products recirculate
- Exposed vent condensate freezing and blocking the pipe
Check in this order
- Keep the vent termination at least 6 ft from adjacent walls.
- Keep it at least 5 ft below any roof overhang.
- Keep it at least 3 ft above any forced air intake within 10 ft.
- Keep it at least 48 in below or horizontally from any door, window or other gravity air inlet.
- Keep it at least 4 ft horizontally from electric meters, gas meters, regulators, relief valves or other equipment.
- Do not terminate above a door or window or under a deck.
- Do not terminate over a public walkway or where condensate or vapor could be a nuisance.
- Keep the external vent within the maximum length shown in the piping length table.
- Use braces no more than 24 in apart on exposed external pipe up to 4 ft long.
- If external pipe is longer than 4 ft, enclose it in insulation and bring the termination out through the enclosure.
- Point the vent elbow outward, away from the air inlet, not sideways.
- Keep the termination out of building corners, window wells, stairwells, alcoves and courtyards.
Applies to: SF-550 and SF-750 direct exhaust, sidewall termination
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series 3 commercial gas-fired water boiler manual, p. 32-33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.