Viessmann · Boiler troubleshooting
Check expansion vessel pre-charge and system pressure
What is going on
Carry out this check on a cold system and follow the expansion vessel manufacturer's instructions. Permissible operating pressure is 80 psi (5.5 bar).
Likely causes
- Pre-charge lower than static system pressure
Check in this order
- Drain the system until the manometer reads 0, or close the cap valve on the expansion vessel and reduce the vessel pressure.
- If the pre-charge is lower than the static system pressure, top up with nitrogen until the pre-charge is 1 to 2 psi (0.1 to 0.2 bar) higher.
- Top up with water until the cooled system charge pressure is 1 to 2 psi (0.1 to 0.2 bar) higher than the vessel pre-charge.
- Confirm the system stays below 80 psi (5.5 bar).
Applies to: Vitocrossal 200 CI2 boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 Service Instructions, p. 35. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.