Viessmann · Boiler troubleshooting

Check expansion vessel pre-charge and system pressure

Vitocrossal 200 CI2

What is going on

Carry out this check on a cold system and follow the expansion vessel manufacturer's instructions. Permissible operating pressure is 80 psi (5.5 bar).

Likely causes

  • Pre-charge lower than static system pressure

Check in this order

  1. Drain the system until the manometer reads 0, or close the cap valve on the expansion vessel and reduce the vessel pressure.
  2. If the pre-charge is lower than the static system pressure, top up with nitrogen until the pre-charge is 1 to 2 psi (0.1 to 0.2 bar) higher.
  3. Top up with water until the cooled system charge pressure is 1 to 2 psi (0.1 to 0.2 bar) higher than the vessel pre-charge.
  4. Confirm the system stays below 80 psi (5.5 bar).

Applies to: Vitocrossal 200 CI2 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 Service Instructions, p. 35. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.