Viessmann · Boiler troubleshooting
Check CO2 and O2 at start-up and service
What is going on
The burner is factory set for natural gas and needs no adjustment. Only check CO2 and O2 at the vent adaptor.
Check in this order
- Connect a flue gas analyzer to test port A on the vent pipe adaptor.
- Open the gas shut-off valve, start the boiler and create a heat demand.
- Enter the service actuator test and select base load (low fire). Measure CO2 and O2.
- Compare readings with the ranges in the CO2/O2 table for the gas type.
- Enter the measured values in the Maintenance Record (p. 96).
- End the test by selecting all actuators off.
- Select full load (high fire). Measure CO2 and O2 again and compare with the ranges.
- Exit the actuator test and record the values (p. 97).
Applies to: Vitodens 200-W B2HA natural gas and LPG
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.