Thermostat calling but boiler not firing
What is going on
Call for heat present but no burner.
Likely causes
- Supply water already above set point minus differential (TT / DHW blocking)
- Flue temperature high (E07)
- Low water pressure (PRO)
- Flue pressure switch (FLU)
- Condensate full (F20)
Check in this order
- Read the message on the display and match it to the code list
- Check SUPPLY against CH set minus diff in the status menu
- Check there is no voltage across the thermostat terminals
- Check system pressure over 10 psig
Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Elite EL-80 N Installation Manual (LP-293), p. 66 to p. 68, p. 51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.