Flame drops out while running (F10)
What is going on
Flame lost three times on one call.
Likely causes
- Gas pressure sag
- Dirty or worn flame probes
- Burner gasket leak
Check in this order
- Watch inlet gas pressure under load
- Check FLAME signal in status menu (over 1.0 microamp, steady 5 to 9 after 1 min)
- Clean the rectifier and spark probe; replace both if still weak
- Check burner door gaskets
Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Elite EL-80 N Installation Manual (LP-293), p. 71, p. 72. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.