Lockout on ignition (F09, no flame)

Elite EL

What is going on

Boiler tries to light four times on one call and locks out.

Likely causes

  • Spark electrode gap wrong or corroded
  • No gas / low gas pressure / air in line
  • Dirty flame rectifier
  • Blocked flue or condensate

Check in this order

  1. Watch the igniter through the sight glass
  2. Set electrode gap to 0.196 in. (5 mm +/-1) and clean corrosion
  3. Measure gas inlet pressure; 3.5 to 14 in. w.c. with no more than 1 in. drop on light-off
  4. New or empty LP installs make sure the line was purged
  5. Check the flame rectifier
  6. Check flue and condensate for blockage

Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Elite EL-80 N Installation Manual (LP-293), p. 71, p. 38. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.