HTP · Boiler troubleshooting

False flame signal with burner off (F11)

Elite EL

What is going on

Flame signal present with no call.

Likely causes

  • Leaking gas valve
  • Condensate backup
  • Refractory touching probe

Check in this order

  1. Look in the sight window; if lit, shut the gas and replace the valve
  2. Check condensate path and the refractory wall
  3. Replace igniter and rectifier if signal remains over 1.0 with burner off

Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Elite EL-80 N Installation Manual (LP-293), p. 72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.