HTP · Boiler troubleshooting
False flame signal with burner off (F11)
What is going on
Flame signal present with no call.
Likely causes
- Leaking gas valve
- Condensate backup
- Refractory touching probe
Check in this order
- Look in the sight window; if lit, shut the gas and replace the valve
- Check condensate path and the refractory wall
- Replace igniter and rectifier if signal remains over 1.0 with burner off
Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Elite EL-80 N Installation Manual (LP-293), p. 72. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.