Boiler overheating lockout (F00, F05, F06)

Elite EL

What is going on

Water temperatures running too high and boiler locking out with the pump running.

Likely causes

  • Circulator failed or wrong direction
  • Closed valves, no water or low flow
  • Failed ECO or thermistor

Check in this order

  1. Check the circulator runs and flows the right way
  2. Confirm water in system and valves open
  3. Confirm less than 50 F rise from return to supply in the status menu
  4. Check thermistor resistance against the chart
  5. Check ECO wiring; replace ECO if water is not hot

Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Elite EL-80 N Installation Manual (LP-293), p. 69, p. 70. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.