HTP · technician tips
HTP service menus, test modes and resets
9 tips for boiler: access codes, button combinations, test modes and the resets you need at the appliance.
Jump to: Access & passwords (1) · Service & test modes (2) · Reset & cancel (2) · Commissioning (3) · Other (1)
Access & passwords
Installer and service menu codes, and how to get into them.
Service & test modes
Forced fan, low and high fire, test and diagnostic modes, error history and live data.
Pump service mode to purge air
Boiler · Elite EL
Run each pump by hand to bleed the system.
- Disconnect the wires on the THERMOSTAT terminals
- Apply power
- Press the down arrow and ENTER together for 1 second: CH pump runs
- Press the up arrow: DHW pump; again: system pump (cascade master)
- Down and up together returns to normal
Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)
Source: Elite EL-80 N Installation Manual (LP-293), p. 50. Written in our own words; check the manual for your exact model.
Test mode (fixed-fire, gas pressure and combustion)
Boiler · Elite EL
Run the boiler outside normal modulation.
- Create heat demand by opening zones
- Press the up arrow and ENTER together for 1 second
- Boiler goes through ignition, then use up/down to raise or lower fan speed (SERVICE RUN rpm)
- Exit with up and down arrows together; exits by itself after 20 minutes
Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)
Source: Elite EL-80 N Installation Manual (LP-293), p. 63, p. 64. Written in our own words; check the manual for your exact model.
Reset & cancel
Clearing lockouts, service reminders and fault history; skipping purge or de-air programs.
Reset a lockout
Boiler · Elite EL
How to clear fault lockouts.
- Fix the cause first
- Press RESET for more than 1 second
- F01 with LWCO: reset the LWCO box first, then the display
- F01 flue switch: push the red button on the switch (flue below 90 F)
- PP: press RESET to start the control
Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)
Source: Elite EL-80 N Installation Manual (LP-293), p. 65, p. 69, p. 73. Written in our own words; check the manual for your exact model.
Reset the maintenance reminder
Boiler · Elite EL
Clear MAINTENANCE REQUIRED after service.
- Hold ENTER 3 seconds (code stays 000)
- Press ENTER again to reach SERVICE SCHEDULE RESET
- Use the right arrow to pick Year or Hours
- Press ENTER to reset, adjust with up/down, press ENTER
Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)
Source: Elite EL-80 N Installation Manual (LP-293), p. 59. Written in our own words; check the manual for your exact model.
Commissioning
Start-up and set-up steps that are easy to miss.
Cascade set-up
Boiler · Elite EL
Address boilers for a cascade.
- Master: function 15 = 0, function 23 = 926 Boiler
- Followers: function 15 = 1, 2, ... (no duplicates), function 23 = 926 Boiler
- A follower with an indirect tank must be address 2 or higher
- Master and follower set points must match
- Daisy-chain CAT3/CAT5 cables, max 200 ft
Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)
Source: Elite EL-80 N Installation Manual (LP-293), p. 52, p. 57, p. 43. Written in our own words; check the manual for your exact model.
Check thermostat circuit for stray voltage
Boiler · Elite EL
Common wiring fault with zone valves.
- Disconnect the two thermostat wires from the boiler
- Meter across them with thermostats and zone valves closed one at a time
- There must be no voltage
- Fix external wiring if any voltage shows
Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)
Source: Elite EL-80 N Installation Manual (LP-293), p. 51. Written in our own words; check the manual for your exact model.
Start-up combustion and gas checks
Boiler · Elite EL
Items to record at light-off.
- Static and light-off drop gas pressure (3.5 to 14 in. w.c., max 1 in. drop)
- Flame current at high and low fire
- CO2 and CO at high and low fire against the combustion table
- Fill condensate trap with water before first start
- Pressurize 12 to 15 psi
Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)
Source: Elite EL-80 N Installation Manual (LP-293), p. 79, p. 64. Written in our own words; check the manual for your exact model.
Other
Everything else worth knowing at the appliance.
Read fault history
Boiler · Elite EL
Last ten lockouts with date and time.
- From the default screen press the right arrow
- Press the down arrow to step through the status screens
- The last ten lockouts follow, newest first, alternating with the fault code
Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)
Source: Elite EL-80 N Installation Manual (LP-293), p. 60, p. 62. Written in our own words; check the manual for your exact model.
Related
Same tips in your pocket
The HVACopedia app has these tips, every error code and the settings tables offline.
For licensed technicians. Installer menus, test modes and access codes change settings that affect safety; only use them if you are trained on the appliance and understand the result. Gas, electrical and refrigerant work must be done by a qualified, licensed person, and the manufacturer’s manual for the exact model and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.