Propane conversion procedure

SVF 500/600 Series 1

What is going on

Converts an SVF boiler from natural gas to propane. The boiler ships set for natural gas and needs a propane orifice and propane venturi, sold as a separate kit (part 384000423). Shut off power and close the external manual gas valve before starting. Allow the boiler to cool if it has been running. Test the boiler fully afterward.

Check in this order

  1. Shut off power to the boiler and close the external manual gas shut-off valve.
  2. Check the stamping on the propane orifice plate against the boiler size. The SVF 500/600 orifice is 0.494 in.
  3. Check the propane venturi orifices top 6.6 mm, bottom 8.4 mm. The venturi label should read Venturi 45 and Inj 840/660.
  4. Set the gas valve throttle coarsely open fully, then close 4 and 7/8 turns.
  5. Remove the two top panels and the side panels for access.
  6. Remove the four 8 mm bolts holding the silencer to the venturi.
  7. Disconnect the gas flex line from the inlet pipe of the automatic gas valve.
  8. Remove the four bolts (8 mm wrench and 4 mm Allen) holding the gas pipe to the bottom of the venturi. A gasket will come loose.
  9. Remove the natural gas venturi and its O-ring from the blower (13 mm wrench). Discard the venturi and check the O-ring; replace it if damaged.
  10. Install the propane venturi on the blower with the gas connection pointing down and the O-ring seated. Tighten the three blower nuts (at 12, 4 and 8 o'clock, 120 degrees apart) to 87 in-lbs (9.82 Nm).
  11. Install the propane orifice plate between the gas pipe and the side port of the venturi, between the two square gaskets from the kit. Tighten the gas pipe to 44 in-lbs (5.0 Nm).
  12. Reinstall the silencer with the four bolts and tighten to 44 in-lbs (5.0 Nm).
  13. Reconnect the gas flex line to the automatic gas valve inlet pipe.
  14. Apply the conversion label next to the rating label.
  15. Restore power. Test the boiler completely, fill out the Fire Test label, and check combustion levels and operation of the boiler and all system components.

Applies to: SVF 500 and SVF 600 boilers converting to propane

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 boiler manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.