Viessmann · Boiler troubleshooting

Clear the Service message after maintenance

Vitotronic 200

What is going on

Used when the Service display and red fault indicator flash because a service limit was reached. Coding address 24 holds the service timer and must be reset after the work is done.

Likely causes

  • Service limit set by coding addresses 1F, 21 or 23 has been reached

Check in this order

  1. If service is done before Service is shown, set coding address 24:1 and then 24:0 to reset the service hours and interval to 0.
  2. Press the scan button to start the service scan.
  3. Scan through the service messages with the arrow buttons if more than one is stored.
  4. Confirm 'Acknowledge: Yes' to turn off the Service display. The red fault indicator keeps flashing.
  5. Press the scan button again to end the service scan.
  6. After maintenance, set coding address 24 back to 24:0. The red fault indicator then goes off.
  7. If 24 is not reset, the Service display returns at 07:00 on Monday.
  8. Reset burner operating hours, burner starts and fuel consumption as shown in the operating status section.
  9. Reset the maximum flue gas temperature to the current value using the held button combination (about 4 seconds), then confirm.

Applies to: Vitotronic 200 KW2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 Service Instructions, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.