Viessmann · Boiler troubleshooting
System version 5: heating circuit with one low temperature circuit
What is going on
Vitocrossal 300 controlled by a Viessmann boiler control with outdoor reset, modulating boiler water temperature and load-dependent sequential control of two-stage or modulating burners. The Vitocrossal 300 has two return connections; higher return temperature circuits go to the upper connection and lower return temperature circuits go to the lower connection. The LON-BUS sets the boiler supply temperature from the highest mixing valve circuit temperature plus an adjustable differential.
Check in this order
- Connect at least 15% of the rated output to the lower return connection.
- Code every Vitotronic 100 GC1 as shown in the system version 5 coding table.
- Check the connection diagram on site for completeness and function, because it is only a recommendation.
- Wire single-phase and three-phase pumps through field-supplied motor contactors or starters.
Applies to: System version 5, Vitocrossal 300
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 18-20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.