Weil-McLain · Boiler troubleshooting

Metal flakes in the flue ways (oil water boiler)

Weil-McLain WGO Series 4

What is going on

Corrosion or flaking in the flue passages.

Likely causes

  • Chemicals near the boiler (bleach, cleaners, sprays, fabric softener, paint remover) getting into combustion air
  • Flue gas condensing in the flue ways

Check in this order

  1. Remove those products from the boiler area.
  2. Check the nozzle and pump pressure for the right firing rate.
  3. Set combustion with an analyzer and clean the flue ways.

Applies to: WGO-2 to WGO-9 oil-fired water boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain WGO Series 4 Water Boiler Manual 550-142-331/0225, Troubleshooting p.7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.