Navien · Boiler troubleshooting

First-time lighting and gas shutdown procedure

NCB700

What is going on

Pilotless boiler with electronic ignition. Smell for gas before every start, and never light the burner by hand. The gas control knob is turned by hand only.

Check in this order

  1. Do not light the burner by hand. The boiler uses electronic ignition.
  2. Before operating, smell all around the appliance and next to the floor for gas. Propane and natural gas can settle low.
  3. If gas is smelled, do not operate any appliance or switch, do not use a phone in the building, call the gas supplier from outside, and call the fire department if the supplier cannot be reached.
  4. Turn off electrical power to the boiler.
  5. Set the thermostat or control to its lowest setting.
  6. Close the main manual gas valve and wait 5 minutes for any gas to clear. Smell again before continuing.
  7. Open the main manual gas valve.
  8. Turn electrical power on and set the thermostat to the desired setting.
  9. To shut off gas to the boiler for service: turn off electrical power, set the thermostat to lowest, then close the main manual gas valve.
  10. Do not use the boiler if any part was under water. Have a licensed professional inspect it and replace the submerged gas control and control parts.

Applies to: NCB700 combi-boiler, all models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation & operation manual, p. 112. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.