Viessmann · Boiler troubleshooting

Brief scan (short query) overview

Vitocrossal 300 CA3B Dual Fuel

What is going on

The short query shows 11 lines and 6 fields with system identification, KM BUS participants, software versions, remote control type, LON and heating circuit data. Field 3 and field 5 show the same display.

Check in this order

  1. From the home screen tap Menu, then Service.
  2. Enter the viservice password.
  3. Tap Diagnosis, then Short query.
  4. Read the control unit software version, appliance ID (CU-ID), KM BUS participant count and extension software versions as needed.
  5. Check remote control type (0 none, 1 Vitotrol 200A, 2 Vitotrol 300A) and the heating circuit entries.

Applies to: Brief scan

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Service Instructions, p. 117. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.