Example F field wiring between master and shadow boilers

Evergreen Pro Series 2

What is going on

Wiring layout for the master and shadow boilers, including sensors, zone outputs and valves.

Check in this order

  1. Connect the master boiler and each shadow boiler in the order shown: master to shadow 2, shadow 2 to shadow 3, and shadow 3 to shadow 4.
  2. On each boiler, wire the zone thermostats to the zone inputs and the zone circulators or valves to the matching numbered outputs.
  3. Wire the boiler isolation valve (item 17a) to output 4 on the master and each shadow that uses it.
  4. On shadow 3, wire the bypass valve (item 17b) to output 3.
  5. Wire the outdoor air sensor, system supply sensor and system return sensor to the J19 or J16/J17 terminals as shown in the diagram. Sensors marked * are for redundancy only and are not required.
  6. Check that each boiler's 120 VAC outputs stay within 2.2 A and use an external relay where the valve or load needs it.

Applies to: Example F multi-boiler wiring, Figures 18 and 19 context

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Series 2 advanced manual 550-100-581/0325, p. 42-43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.