Example F field wiring between master and shadow boilers
What is going on
Wiring layout for the master and shadow boilers, including sensors, zone outputs and valves.
Check in this order
- Connect the master boiler and each shadow boiler in the order shown: master to shadow 2, shadow 2 to shadow 3, and shadow 3 to shadow 4.
- On each boiler, wire the zone thermostats to the zone inputs and the zone circulators or valves to the matching numbered outputs.
- Wire the boiler isolation valve (item 17a) to output 4 on the master and each shadow that uses it.
- On shadow 3, wire the bypass valve (item 17b) to output 3.
- Wire the outdoor air sensor, system supply sensor and system return sensor to the J19 or J16/J17 terminals as shown in the diagram. Sensors marked * are for redundancy only and are not required.
- Check that each boiler's 120 VAC outputs stay within 2.2 A and use an external relay where the valve or load needs it.
Applies to: Example F multi-boiler wiring, Figures 18 and 19 context
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Series 2 advanced manual 550-100-581/0325, p. 42-43. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.