Viessmann · Boiler troubleshooting
Connecting boiler pumps (shunt, boiler circuit, DHW)
What is going on
Pump wiring to the boiler control. Line-voltage pumps are switched through a contactor or motor starter.
Check in this order
- Use terminals 6-L, 6-G and 6-N in the line voltage connection enclosure for the shunt or boiler circuit pump.
- For a 120 VAC DHW tank pump or shunt pump, use the connection marked B on the connection enclosure.
- For 240 VAC or 3-phase pumps, do not power the pump direct; use a contactor and/or motor starter.
- Select the contactor and connecting wire to suit the pump rating. Contactor activation rating: max 2 FLA. Recommended wire size AWG 14.
- Connect pump and power supply to the contactor, then connect the contactor coil to the corresponding terminals.
- Install pumps per the pump manufacturer's instructions and follow local and national wiring codes.
Applies to: Vitotronic 100 GC1 boiler control pump outputs
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 36. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.