Viessmann · Boiler troubleshooting

Connecting boiler pumps (shunt, boiler circuit, DHW)

Vitotronic 100 GC1

What is going on

Pump wiring to the boiler control. Line-voltage pumps are switched through a contactor or motor starter.

Check in this order

  1. Use terminals 6-L, 6-G and 6-N in the line voltage connection enclosure for the shunt or boiler circuit pump.
  2. For a 120 VAC DHW tank pump or shunt pump, use the connection marked B on the connection enclosure.
  3. For 240 VAC or 3-phase pumps, do not power the pump direct; use a contactor and/or motor starter.
  4. Select the contactor and connecting wire to suit the pump rating. Contactor activation rating: max 2 FLA. Recommended wire size AWG 14.
  5. Connect pump and power supply to the contactor, then connect the contactor coil to the corresponding terminals.
  6. Install pumps per the pump manufacturer's instructions and follow local and national wiring codes.

Applies to: Vitotronic 100 GC1 boiler control pump outputs

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 36. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.