Viessmann · Boiler troubleshooting

Connect a low water cut-off device

Vitotronic 300

What is going on

Wire the LWCO switch contact into the safety circuit at plug aBÖ.

Check in this order

  1. Remove the jumper between terminals 21(L) and 22(L).
  2. Connect the LWCO switching contact to terminals 21(L) and 22(L).
  3. Power the low water cut-off device from a free terminal 14, 15, 16 or 17 (L, N, G).
  4. Refer to the LWCO manufacturer manual for interconnection details.

Applies to: Vitotronic 300 GW6B

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300, GW6B installation and service instructions, p. 36. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.