Example B multi-boiler field wiring (master and shadows)

Evergreen Series 2

What is going on

Power goes to the master boiler at 120 VAC through the L1 hot, neutral and ground terminals. The boiler circulator connects to the BOILER PUMP terminals and its 2-pin plug at J4-4, rated 2.2 A max on the output. Each zone circulator output is rated 2.0 A max with black, white and green leads. Zone thermostats land on the W, R and C terminals of each zone. Outdoor air and system supply/return sensors land on the TT inputs and J19. Sensors marked with an asterisk are for redundancy only and are not needed.

Check in this order

  1. Connect 120 VAC power to the L1 HOT, L1 NEUTRAL and L1 GROUND terminals.
  2. Wire the boiler circulator to the BOILER PUMP terminals and the 2-pin plug at J4-4.
  3. Wire each zone circulator to its numbered output, keeping the black, white and green leads together.
  4. Wire each zone thermostat to its W, R and C terminals.
  5. Wire the outdoor air and system supply/return sensors to the TT inputs and J19 as labeled.
  6. Wire the shadow boilers the same way, following the layout for Shadow 2, 3 and 4 on the page.

Applies to: Example B multi-boiler, master and shadow boilers 2 to 4

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.