Viessmann · Boiler troubleshooting
Boiler disable external control
What is going on
A dry contact on the plug aVD takes the boiler out of the boiler sequence.
Check in this order
- Connect a dry contact to terminals 1 and 2 of plug aVD.
- Contact closed the burner is disabled, the isolation/return valve closes, and the shunt pump or boiler circuit pump switches off. Other boilers must supply the heat.
- Contact open the boiler returns to the current boiler sequence.
Applies to: Boiler disable contact
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.