Viessmann · Boiler troubleshooting

Boiler disable external control

Vitotronic 100 GC1

What is going on

A dry contact on the plug aVD takes the boiler out of the boiler sequence.

Check in this order

  1. Connect a dry contact to terminals 1 and 2 of plug aVD.
  2. Contact closed the burner is disabled, the isolation/return valve closes, and the shunt pump or boiler circuit pump switches off. Other boilers must supply the heat.
  3. Contact open the boiler returns to the current boiler sequence.

Applies to: Boiler disable contact

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 51. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.