Weil-McLain · Boiler troubleshooting
Pipe a closed-type expansion tank
What is going on
Closed-type tanks rely on an air cushion that must stay in the system. Piping must allow that air to return to the tank.
Likely causes
- Air trapped in horizontal piping
- Air lost through an automatic air vent, causing the tank to water-log
Check in this order
- Use Figure 15 (alternate) for closed-type tank connections.
- Pitch horizontal piping up toward the tank at 1 inch per 5 feet of run.
- Connect to the tank with at least 3/4-inch pipe so air can rise.
- Do not install an automatic air vent on a closed-type tank system.
- Do not use a closed-type tank if a connected water heater has an automatic vent.
Applies to: SlimFit 1000-2000 Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 Boiler Manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.