Weil-McLain · Boiler troubleshooting

Wire 0-10VDC remote target input

ECO Tec Series 3

What is going on

The 0-10VDC signal adjusts the supply target temperature and replaces the outdoor sensor as the target modifier.

Check in this order

  1. Connect the 0-10VDC signal to J16 pins 5 (common) and 6 (positive).
  2. Assign a priority to a dry contact heat demand input. A dry contact demand is required to start a call for heat.
  3. Use PRIORITY 1 for indirect DHW (default values are for direct-piped indirect DHW). Use PRIORITY 2 for heating systems, or PRIORITY 2 or 3 on combi.
  4. Set TARGET ADJUST to 0-10V for the priority used.
  5. Set the voltage and temperature points (see the 0-10VDC target settings table).
  6. Between the max and min voltage points, the target temperature changes in proportion.

Applies to: ECO Tec Series 3 all models with 0-10VDC modulation

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.