Rinnai · Boiler troubleshooting
Vent termination location rules
What is going on
Terminations must be at least 12 in. above ground or the expected snow level. Keep them away from dryer vents, commercial cooking exhaust and air inlets. Do not terminate over public walkways, near soffit or crawl space vents, or where condensate or vapour could cause a nuisance, damage, or harm regulators or relief valves. Under a soffit or eave, keep exhaust out of soffit vents, keep it clear of where moisture collects, and do not place it so close that exhaust recirculates into the combustion air intake. Local code can be stricter than these clearances. Category IV horizontal runs must slope up at least 1/4 in. per foot toward the terminal, prevent condensate pooling, and provide drainage where needed.
Check in this order
- Confirm the termination is at least 12 in. above ground or expected snow level.
- Check the location against dryer vents, commercial cooking exhaust and air inlets.
- Avoid walkways, soffit and crawl space vents, and areas where condensate or vapour can cause damage.
- Under eaves, check exhaust cannot enter soffit vents or recirculate into the combustion air intake.
- Slope Category IV horizontal runs up at least 1/4 in. per foot toward the terminal and provide drainage for condensate.
Applies to: I-Series Plus vent terminations
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.