Viessmann · Boiler troubleshooting
Service the burner refractory and cylinder burner
What is going on
Check the refractory ring and cylinder burner for damage and replace as needed.
Check in this order
- Remove the electrode block and ionization electrode A.
- Undo the three retaining clips B and remove refractory ring C.
- Loosen the four Torx screws D and remove cylinder burner assembly E and assembly gasket F.
- Fit a new cylinder burner assembly and new assembly gasket. Tighten to 3.3 lb.ft (4.5 Nm).
- Refit refractory ring C and secure it with retaining clip B.
- Refit the electrode block and ionization electrode A. Tighten to 2.6 lb.ft (3.5 Nm).
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.