Combustion air contamination check
What is going on
Corrosive contaminants in the boiler room or the combustion air source can damage the burner and heat exchanger. Check the room and the air source before installing, and pipe air from outside if contaminants are present.
Likely causes
- Chlorinated or fluorinated products such as spray cans, waxes, cleaners, pool chemicals, or refrigerant leaks
- Solvents, paint or varnish removers, glues, cements, or adhesives in the air supply
- Drywall and construction dust, or heavy dust and dirt
- Air sources near dry cleaning, pool, metal fabrication, beauty, refrigeration, auto body, plastics, or refinishing areas
Check in this order
- For direct exhaust (inside air), confirm the boiler room and combustion air source are free of contaminants.
- For direct vent, run the air inlet pipe so it cannot pull in contaminated air.
- Do not operate the boiler during construction unless the air inlet is piped from a dust-free, contaminant-free area.
- Compare the room against the contaminant list in Figure 21 before deciding on inside air.
Applies to: SlimFit SF1000, SF1500, SF2000 Series 2 boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit 1000-2000 Series 2 boiler manual, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.