Weil-McLain · Boiler troubleshooting

Combustion air contamination check

SlimFit Series 2

What is going on

Corrosive contaminants in the boiler room or the combustion air source can damage the burner and heat exchanger. Check the room and the air source before installing, and pipe air from outside if contaminants are present.

Likely causes

  • Chlorinated or fluorinated products such as spray cans, waxes, cleaners, pool chemicals, or refrigerant leaks
  • Solvents, paint or varnish removers, glues, cements, or adhesives in the air supply
  • Drywall and construction dust, or heavy dust and dirt
  • Air sources near dry cleaning, pool, metal fabrication, beauty, refrigeration, auto body, plastics, or refinishing areas

Check in this order

  1. For direct exhaust (inside air), confirm the boiler room and combustion air source are free of contaminants.
  2. For direct vent, run the air inlet pipe so it cannot pull in contaminated air.
  3. Do not operate the boiler during construction unless the air inlet is piped from a dust-free, contaminant-free area.
  4. Compare the room against the contaminant list in Figure 21 before deciding on inside air.

Applies to: SlimFit SF1000, SF1500, SF2000 Series 2 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit 1000-2000 Series 2 boiler manual, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.