Remote target operation (0-10 VDC) priority settings
What is going on
Remote target lets an analog input set the supply temperature for any priority, including network priorities. Target vs voltage is shown in Figure 56 on page 64.
Check in this order
- In the priority menu, set TARGET ADJUST to 0-10v.
- Set VOLTS FOR MIN to the voltage that gives the desired minimum supply temperature.
- Set VOLTS FOR MAX to the voltage that gives the desired maximum supply temperature.
Applies to: SF1000L/R, SF1500L/R, SF2000L/R
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.