Weil-McLain · Boiler troubleshooting
Gas supply piping connection to the boiler
What is going on
Connect the gas line at the boiler without twisting the factory gas connection.
Check in this order
- Use two wrenches one holds the boiler gas connection still while the other tightens the joint.
- Install a union for servicing where required.
- Install a manual gas shut-off valve in the supply line within 6 ft of the boiler. In Canada, the installer must identify this valve.
- Support the gas piping with hangers. Do not support it from the boiler or its accessories.
- Use pipe dope compatible with propane, since natural gas may contain some propane. Apply sparingly to male threads only so it does not block gas flow.
- The boiler ships ready for natural gas only. Install the propane conversion kit before connecting propane (see p. 16).
- If any factory gas connection is altered, check for leaks before operating the boiler (p. 63).
Applies to: SVF 500/600 gas supply piping
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 62. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.