Navien · Boiler troubleshooting

Condensate neutralizer kit installation and maintenance

NCB700

What is going on

Use a neutralizer when condensate is discharged through an approved neutralizing agent. The agent must be replaced periodically, and the boiler's firing rate sets how fast it is used up. Navien's neutralizer kit is recommended. Flue gases must never pass through the neutralizer. Only one appliance may connect to each neutralizer.

Check in this order

  1. Mount the neutralizer on a wall or floor and secure it with the kit brackets before final connection.
  2. Install the neutralizer with its inlet and outlet closer to the floor than the condensate drain.
  3. Make the inlet connection at the center point and the outlet at the offset connection.
  4. If installed horizontally, rotate it so the outlet is at the highest point. If installed vertically, keep the outlet above the inlet.
  5. Install an overflow bypass between the boiler and the neutralizer to prevent condensate from flowing back into the boiler.
  6. Install a Y-fitting for blockage protection and make sure the drain flows freely.
  7. Make sure the outlet connection is accessible for service and pH checks.
  8. If the slope is insufficient, install a condensate pump designed for boilers and water heaters.
  9. During the first year, inspect the neutralizer every few months and replace it when needed.
  10. Check the pH at the outlet at least once a year with approved test strips or an electronic pH meter.
  11. Replace the agent when pH drops below the local water utility minimum, or below 6.0 if no minimum is given.
  12. Each year, clean the condensate trap and refill it with fresh water through the access point.

Applies to: NCB700 with condensate neutralizer

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 193-194. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.