Viessmann · Boiler troubleshooting
Replacing the burner fan
What is going on
Removing the fan and Venturi pipe with gas valve, then refitting.
Check in this order
- Disconnect both connectors from the fan.
- Remove the 6 nuts on the Venturi pipe and lift off the Venturi pipe with the fitted gas valve (torque 4.5 lb.ft / 6 Nm on refit).
- Undo the hex nuts from the 4 studs.
- Remove the fan and note how the gasket sits.
- Refit in reverse order and make sure the gasket is in the correct position.
Applies to: Vitocrossal 300 CA3B Dual Fuel burner fan
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.