Flow rate outside boiler limits or unknown

Vitodens 200-W

What is going on

System flow is above the boiler maximum, below the minimum, or not known. Viessmann recommends a low-loss header in this case.

Likely causes

  • System flow exceeds boiler maximum flow rate.
  • System flow falls below boiler minimum flow rate.
  • System flow rate is unknown.

Check in this order

  1. Check the boiler maximum flow rate for the model (25 GPM / 5700 L/h).
  2. Compare the system flow rate to the boiler limits.
  3. Install a low-loss header if the flow is out of range or unknown.
  4. Use the flow tables to see how many boilers in a cascade fit the flow.

Applies to: Vitodens 200-W B2HA 80-100, 285-352

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA installation instructions, p. 30-31. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.