Flow rate outside boiler limits or unknown
What is going on
System flow is above the boiler maximum, below the minimum, or not known. Viessmann recommends a low-loss header in this case.
Likely causes
- System flow exceeds boiler maximum flow rate.
- System flow falls below boiler minimum flow rate.
- System flow rate is unknown.
Check in this order
- Check the boiler maximum flow rate for the model (25 GPM / 5700 L/h).
- Compare the system flow rate to the boiler limits.
- Install a low-loss header if the flow is out of range or unknown.
- Use the flow tables to see how many boilers in a cascade fit the flow.
Applies to: Vitodens 200-W B2HA 80-100, 285-352
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA installation instructions, p. 30-31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.