Viessmann · Boiler troubleshooting
Connect 1st stage burner switch (plug aVD, terminals 1 and 2)
What is going on
Dry contact that switches the basic-load burner stage.
Check in this order
- Disconnect power before wiring.
- Connect a dry contact to terminals 1 and 2 of plug aVD.
- Contact closed the 1st stage burner runs. On VD2/VD2A the full load only runs to hold minimum temperature, not with Vitocrossal 300.
- Water temperature is limited by the electronic max limit (coding 06) if set below the mechanical high limit R.
- Contact open the 1st stage burner turns off.
Applies to: VD2/VD2A and CT3 with external modulation controller
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 41, 43. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.