Viessmann · Boiler troubleshooting

Connect 1st stage burner switch (plug aVD, terminals 1 and 2)

Vitotronic 300

What is going on

Dry contact that switches the basic-load burner stage.

Check in this order

  1. Disconnect power before wiring.
  2. Connect a dry contact to terminals 1 and 2 of plug aVD.
  3. Contact closed the 1st stage burner runs. On VD2/VD2A the full load only runs to hold minimum temperature, not with Vitocrossal 300.
  4. Water temperature is limited by the electronic max limit (coding 06) if set below the mechanical high limit R.
  5. Contact open the 1st stage burner turns off.

Applies to: VD2/VD2A and CT3 with external modulation controller

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 41, 43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.