Weil-McLain · Boiler troubleshooting

Check for contaminated combustion air

SlimFit Series 2

What is going on

Corrosive contaminants in combustion air can damage the boiler. Dust from construction is also a problem.

Likely causes

  • Chlorine or fluorocarbon products near the intake
  • Refrigerant or solvent fumes near the intake
  • Excessive dust or dirt, including drywall dust during construction
  • Air intake located near pools, dry cleaners, auto body or similar areas

Check in this order

  1. Keep the boiler off during construction unless combustion air is piped from a dust-free and contaminant-free area.
  2. Review the products and areas listed in Figure 21 (page 24) before choosing the air source.
  3. Do not terminate direct vent air piping where it can draw in contaminated air.
  4. For direct exhaust, keep the boiler room and the combustion air source free of contaminants.
  5. Confirm the air intake is not located in a garage, workshop, laundry or similar area with listed contaminants.

Applies to: SlimFit 1000-2000 Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.