Viessmann · Boiler troubleshooting

Set the adjustable high limit to 189 ºF / 87 ºC

Vitotronic 300

What is going on

Change the dial stop on the adjustable high limit selector knob.

Check in this order

  1. Lever out the selector knob behind the hinged cover with a suitable screwdriver.
  2. Break off the respective cams on the dial with pointed pliers.
  3. Refit the selector knob so the marking sits between 75 and 90.
  4. Turn the selector knob fully clockwise.
  5. Check the box in the Vitotronic 300 service instructions.

Applies to: Vitotronic 300 adjustable high limit

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 installation instructions, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.