Mechanical room prep before installing the boiler
What is going on
Checks the room and site must meet before the Vitocrossal 200 CI2 boiler is set and connected.
Check in this order
- Use the installation room only for the boiler.
- Set the boiler on a load-bearing base at least 4 in. (100 mm) high, and allow for the condensate drain height.
- Place the boiler in a heated indoor space, near a floor drain and as close as practical to the vertical chimney or vent.
- Where possible, locate it near an outside wall so fresh air can be ducted straight to the boiler area.
- Keep the room free of flammable gases and vapors, halogens, solvent vapors and chemical storage.
- Check that the combustion air is clean; in pools, watch for chlorine and salts from water treatment.
- Do not use exhaust fans unless fresh combustion air is supplied (for example a fresh air fan).
- Do not install the boiler in a room with refrigeration equipment.
- Keep humidity low, prevent freezing and ensure good ventilation.
- Keep the mechanical room at or below 104°F (40°C).
Applies to: Vitocrossal 200 CI2 gas condensing boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocrossal 200 CI2 Installation Instructions, p. 8; p. 3. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.