Weil-McLain · Boiler troubleshooting
Combustion air contamination
What is going on
Chlorine or fluorine compounds in intake air form acids in the vent and boiler, which corrode them and can allow flue gas spillage. Products to avoid include chlorinated cleaners and bleaches, pool chemicals, refrigerant leaks, paint removers, muriatic acid, cements, glues and aerosol sprays containing chloro/fluorocarbons. Areas to avoid include laundry rooms, pools, dry cleaners, beauty shops, auto body shops, refrigeration repair shops and new construction.
Likely causes
- Chlorine or fluorine products in combustion air
- Intake located near laundry, pool or other contaminant sources
Check in this order
- Make sure the combustion air will not contain any listed contaminants.
- Remove contaminating products from the boiler room immediately.
- If products cannot be removed, or the intake is in a contaminated area, have the combustion air and vent re-piped to another location by a qualified technician.
- If products have been present for a long time, call a qualified service technician to inspect for acid corrosion.
Applies to: 110/155/220/299/300/399 Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Evergreen Series 2 user's information manual, p. 4, 6. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.