System layout 4: radiator circuit plus underfloor circuit with mixing valve
What is going on
Direct radiator circuit combined with an underfloor circuit on a 3-way mixing valve, plus DHW. The radiator circuit flow must be at least 30% greater than the underfloor flow, and the total must stay under the boiler maximum.
Check in this order
- Confirm the radiator circuit flow is at least 30% greater than the underfloor circuit flow.
- Confirm the combined flow of both circuits stays under the page 30 boiler maximum.
- Use a low-loss header if the flow exceeds the page 30 limit or is unknown.
- Install the mixing valve accessory kit to control the 3-way valve.
- Pipe the DHW circulating pump so it pumps into the boiler.
Applies to: Radiator plus underfloor circuit with mixing valve
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB installation instructions, p. 36. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.