Check system and boiler before first start

CGi Series 5

What is going on

Checks to complete before starting the boiler and before handing it over.

Check in this order

  1. Check system piping for leaks. If found, shut the boiler down and repair immediately.
  2. Vent air from the system with manual vents; air causes poor circulation, uneven heat and noise.
  3. Inspect the vent system for corrosion, physical damage or sagging.
  4. Confirm masonry chimney liners are in good condition, with no obstructions and no openings into the chimney.
  5. Check around the boiler for gas odor using the gas leak check procedure.
  6. Verify operation per the Operation Verification section, then complete the Final Verification Checklist and the installation and service certificate.

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 boiler manual, p. 64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.