External changeover of staged/modulating burner
What is going on
Dry contact at plug aVH selects modulating or two-stage operation.
Check in this order
- Connect a dry contact to terminals 1 and 2 of plug aVH.
- Contact closed modulating operation.
- Contact open two-stage operation. Coding 02: 2 (modulating burner) must be set.
- With the contact closed the burner type scan still shows modulating.
Applies to: Staged/modulating burners
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100, GC1 installation manual, p. 60. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.