Viessmann · Boiler troubleshooting

External changeover of staged/modulating burner

Vitotronic 100GC1

What is going on

Dry contact at plug aVH selects modulating or two-stage operation.

Check in this order

  1. Connect a dry contact to terminals 1 and 2 of plug aVH.
  2. Contact closed modulating operation.
  3. Contact open two-stage operation. Coding 02: 2 (modulating burner) must be set.
  4. With the contact closed the burner type scan still shows modulating.

Applies to: Staged/modulating burners

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100, GC1 installation manual, p. 60. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.