Weil-McLain · Boiler troubleshooting
Replacing manifold orifices
What is going on
Replace the burner orifices only when required, with correctly sized orifices for the gas type. Use a 7/16 inch open-end wrench. Run the final check-out after any orifice change. Do not run the boiler without the burner shield in place.
Likely causes
- Wrong orifice size for the gas type or elevation
- Cross-threaded orifice in manifold tapping
Check in this order
- Remove the burner shield screws and remove the burner shield.
- Using a 7/16 inch open-end wrench, remove the burner orifices from the manifold.
- Apply a small amount of propane-compatible pipe dope to each new orifice.
- Install the new orifices with a 7/16 inch open-end wrench. Align them correctly and do not cross-thread them.
- Reinstall the burner shield. Do not operate the boiler without it.
- Run the final verification checklist (p. 66) to confirm proper operation.
Applies to: CGi-25 to CGi-8
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: CGi Series 5 Gas-Fired Water Boiler Manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.