Navien · Boiler troubleshooting
Installing the condensate neutralizer kit
What is going on
A Navien neutralizer kit is recommended when condensate goes through a neutralizing agent. Flue gases must never pass through the neutralizer. Only one appliance may connect to each neutralizer.
Check in this order
- Mount the neutralizer on a wall or floor with the brackets in the kit.
- Keep the neutralizer inlet and discharge closer to the floor than the condensate drain.
- Horizontal mounting rotate so the outlet is at the highest point.
- Vertical mounting keep the outlet higher than the inlet.
- Install an overflow bypass between the appliance and the neutralizer to stop backflow.
- Use corrosion-resistant piping and secure it so it cannot move.
- Use a Y-fitting for extra safety if the condensate drain blocks, and confirm the condensate still runs freely to the drain.
- Keep the discharge connection accessible for maintenance and pH testing.
- Fill the trap by pouring water into the boiler's exhaust vent until water runs through the condensate drain.
- Keep piping away from freezing temperatures and protect it from pedestrian damage and vibration.
Applies to: NCB700 condensate neutralizer kit
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.