Viessmann · Boiler troubleshooting

Clean condensate trap and check condensate drain

Vitodens 200-W B2HB

What is going on

If condensate does not drain freely it builds up in the bottom of the boiler and causes a burner shut-down (fault message). Keep the drain and trap clear.

Likely causes

  • Blocked condensate trap or drain
  • Condensate not draining freely
  • Another appliance drain connected to the condensate line

Check in this order

  1. Remove the retaining clip from the condensate trap and set it aside.
  2. Disconnect the flexible discharge tubing from the trap.
  3. Remove the condensate trap from the boiler.
  4. Clean out debris and refill the trap with water.
  5. Reinstall the trap and secure it with the retaining clip.
  6. Reconnect the flexible discharge tubing.
  7. Do not connect other drains, such as a water softener backwash, to the Vitodens condensate drain.
  8. Make sure the pipe is vented between the trap and the neutralization unit, if fitted.

Applies to: Vitodens 200-W B2HB 19 to 125 boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB service instructions, p. 26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.