Vent and air plate - mounting and sealing

SVF 500/600 Series 1

What is going on

Fit, seal and fasten the vent and air termination plate.

Check in this order

  1. Cut the flue pipe so it extends through the wall and fully enters the termination socket.
  2. Cut the air pipe so it presses against the stops inside the termination.
  3. Slide the flue and air pipes through the openings, then slide the inside plate onto the pipes.
  4. Position the inside plate so the pipes slope down slightly toward the boiler at 1/4 in per foot.
  5. Mark and drill the four mounting holes, remove the pipes, and mount the inside plate.
  6. Test fit the vent/air termination on the vent pipe. The vent pipe must fully enter the socket and the air pipe must butt against the interior stops.
  7. Apply silicone RTV sealant inside the vent termination, slide it onto the vent pipe, and rotate slightly to spread the sealant.
  8. Fasten the termination with four #10 x 1/2 in sheet metal screws and lock washers.
  9. Seal exterior openings thoroughly with exterior caulk.

Applies to: SVF 500/600 Category IV direct vent, sidewall vent and air plate

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 59-60. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.