Weil-McLain · Boiler troubleshooting
Clean the steam gauge glass
What is going on
Normal steam waterline is halfway up the gauge glass. Clean when needed with pressure low.
Likely causes
- Sediment or scale in the gauge glass
Check in this order
- Make sure boiler pressure is low.
- Close the lower gauge cock.
- Open the pet cock.
- Open the lower gauge cock and flush a small amount of water through the pet cock.
- Close the lower gauge cock, then close the pet cock.
- Reopen the lower gauge cock.
- If the glass breaks, close both gauge cocks and call a technician. Do not fit thin glass tubing.
Applies to: Steam boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Gas-Fired Boilers User Manual 550-100-226/0425, p. 21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.