Weil-McLain · Boiler troubleshooting

Remove the cover plate and inspect the burner

ECO Tec Series 3

What is going on

The cover plate nut count depends on model: four nuts on the 110, five on the 150 and six on the 199. Handle the cover plate and burner assembly carefully so the bottom insulation and seal are not damaged.

Check in this order

  1. Remove the cover plate nuts with a 10mm wrench or socket: four on the 110, five on the 150, six on the 199.
  2. Lift the cover plate assembly straight up until the insulation clears the heat exchanger studs, then pull it forward out of the cabinet.
  3. Place the assembly upside down on a clean, flat surface and watch the blower studs.
  4. Slide the bottom cover plate insulation with integrated seal off the burner and set it aside clean. Replace it if the insulation or seal is damaged.
  5. Remove the burner and its gasket with the T20 Torx driver. Discard the old gasket.
  6. Inspect the burner insulation on the cover plate and replace it if damaged or worn.
  7. Clean the burner flange and cover plate surface to remove all old gasket material.
  8. Inspect the inside of the burner. Brush and vacuum it, or blow air from inside out, rinse with water spray, or swirl in mild laundry detergent water and rinse well.
  9. Inspect the burner exterior. Replace it if visibly damaged.
  10. Get a new burner gasket before reinstalling.

Applies to: ECO Tec Series 3 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 150-151. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.