Viessmann · Boiler troubleshooting

Check the flue gas temperature sensor

Vitotronic 300 GW2

What is going on

Applies to VD2, VD2A and CT3 only. The sensor plugs into socket 15 on the boiler control.

Check in this order

  1. Disconnect plug aG in the terminal compartment of the boiler control.
  2. Measure resistance at terminals 1 and 2 of the plug.
  3. Compare with the table 160 °C / 320 °F about 800, 200 °C / 392 °F about 880.
  4. If the value differs significantly, check the installation and replace the sensor if needed.

Applies to: Flue gas temperature sensor 7450 630 (VD2, VD2A, CT3)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 104. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.