Weil-McLain · Boiler troubleshooting
Remove, clean and reinstall the burner
What is going on
Annual service. The boiler contains ceramic fiber material, so handle it with care.
Check in this order
- Shut off power and close the external manual gas valve.
- Let the boiler cool to room temperature.
- Remove the top rear and middle panels.
- Remove the eight M6 nuts on the burner access plate (11 mm), lift the plate straight up and set it aside.
- Inspect the access plate gasket and replace if damaged.
- Remove the eight M6 nuts on the burner (11 mm) and lift the burner out by the inside baffles. Do not drag the fiber mesh.
- Inspect the graphite burner gasket and replace if damaged.
- Clean the burner by vacuum (do not rub or scrape the mesh) or by water rinse only. Let it dry fully.
- Reinstall the burner one way only, with inside baffles perpendicular and parallel to the boiler sides. Make sure the graphite gasket is in place.
- Tighten the eight burner nuts in the order shown on Figure 109 (page 110) to 7.4 ft-lbs.
- Reinstall the access plate with its gasket aligned to the reliefs, and tighten the eight nuts to 7.4 ft-lbs in the same order.
- Test the boiler with the startup procedure on page 88. If flame or combustion is still unacceptable, replace the burner.
- Verify no leaks around the access plate.
Applies to: SVF 1500-3000 Series 1 boiler
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF Series 1 boiler manual, p. 96-97. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.