Weil-McLain · Boiler troubleshooting
Check gas supply pressure and leaks
What is going on
Check the supply pressure at the gas valve and test the connections for leaks.
Check in this order
- Purge all air from the gas supply piping.
- Check the boiler and its gas connection for leaks before startup.
- Close the manual main shutoff valve during pressure tests below 20 in w.c.
- Disconnect the boiler gas connection from the supply piping for pressure tests above 20 in w.c.
- Use a soapy water bubble test. Never use an open flame.
- Connect a manometer to a hose barb fitting in gas valve port #2 (pressure measurement port).
- With all gas appliances running, verify minimum gas pressure of 3.5 in w.c. with gas flowing at high fire during startup.
- Keep supply pressure far enough below 14 in w.c. so normal variation does not trip the high gas pressure switch.
Applies to: SVF 1500-3000
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 47. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.