Weil-McLain · Boiler troubleshooting

Check gas supply pressure and leaks

SVF Series 1

What is going on

Check the supply pressure at the gas valve and test the connections for leaks.

Check in this order

  1. Purge all air from the gas supply piping.
  2. Check the boiler and its gas connection for leaks before startup.
  3. Close the manual main shutoff valve during pressure tests below 20 in w.c.
  4. Disconnect the boiler gas connection from the supply piping for pressure tests above 20 in w.c.
  5. Use a soapy water bubble test. Never use an open flame.
  6. Connect a manometer to a hose barb fitting in gas valve port #2 (pressure measurement port).
  7. With all gas appliances running, verify minimum gas pressure of 3.5 in w.c. with gas flowing at high fire during startup.
  8. Keep supply pressure far enough below 14 in w.c. so normal variation does not trip the high gas pressure switch.

Applies to: SVF 1500-3000

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 47. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.