Viessmann · Boiler troubleshooting
Conversion to liquid propane gas (LPG)
What is going on
Convert the burner from natural gas to LPG using the LPG kit supplied with the burner. Escaping gas is an explosion risk, so check all fittings for leaks.
Check in this order
- Close the gas shut-off valve.
- Switch off the system ON/OFF switch at the boiler control unit.
- Switch off the main boiler circuit breaker or power supply and prevent reconnection.
- Remove the boiler front cover.
- Undo gas supply fitting A.
- Disconnect compensation tubing B from the venturi tube and gas valve.
- Remove four 8 mm hex nuts and detach the gas valve from flange C.
- Remove and discard O-ring F from the gas valve.
- Install rubberized cork gasket E on the gas valve face.
- Install the LPG orifice D with the pin at the top and to the rear.
- Install a second rubberized cork gasket on top of the orifice.
- Secure gas valve, orifice and gaskets to flange C. Torque nuts diagonally to 17.7 lb-in (2.0 Nm).
- Secure and tighten gas supply fitting A.
- Reconnect compensation tubing B.
- Apply the partial rating plate, the NG-to-LPG-labels and the conversion label as described, and complete the conversion report.
- Check all gas fittings for leaks. Do not let leak spray touch electrical components.
Applies to: Vitocrossal 200 CM2 186 to 311 boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.